Knürr Tecoras – DSLAM Outdoor Cabinet
   
  •Best technology
•Customized solution
•Profen in field – with the required specifications regarding thermal management                               and system integration
           
  Individual Configuration
- Identical basic and add-on modules can   be easily extended in modular form to   multiple combinations
- Future security due to installation space   and adaption for 19”, ETSI, 23” and non-   standard equipment, extensive   accessory range
- Easy transport of individual modules   and add-on at installation site
- Damaged covers can be easily and   service-friendly exchanged

Main Unit
- Basic frame of extruded aluminium   AIMgSi0,5 with die-cast aluminium   corner connectors, polished
- Bottom and top cover, rear panel and   side panels of chrome-plated aluminium   AIMg3, 1,5 und 2 mm, polished

External Covers
- Of 2 mm chrome-plated aluminium   AIMg3
- 2 Side covers

  - Rear cover respect. rear door
- Solar protection roof
- All screwing and connecting elements   on the inside

Doors
Double skinned closed or vented for installation of Tecoras thermal components
- Can be used as front and rear door,   door hinges on right or left
- Strong hidden die-cast aluminium hinges - Swing handle for profile half cylinder   with saw protection
- Triple interlocking system
- The intervening ‘tongue’ in the rack   extrusion ensures high locking pressure   with low assembly input Door locking   with 90º, 135º and 180º

Certified Safety

- The cabinets meet requirements in   accordance with IEC 721, ETS 300 019   and GR-487- CORE
- Minimum 25 dB shielding attenuation in   accordance with IEC 61 587-3
- Earthquake-proof to zone 4 in   accordance with Telcordia
   GR-63-CORE
- Vibration test in accordance with
   IEC 68-2-6, IEC 68-2-29
- Environmentally tested in accordance   with IEC 68-2-1, IEC 68-2-2, IEC 68-2-5,   IEC 68-2-56, IEC 60 529

EMC Shielding
Optionally
 

IP Protection Rating
- IP 55

External Cover Finish
Powder-coated, RAL 7035 lightgrey,
outdoor quality in accordance with GSB International, coarse texture

Load Rating
Static up to 4000 N

Integrated Thermal Management
- Wide Range of filter Fan and additive   and integrated heat exchange solutions
- The patented integration of the heat   exchanger in the enclosure wall   ensures an increase of the available   usage space by more than 15%
- Extensive cooling for the first
  time with low cabinet depths
  (‹ 400 mm) for use in public
  access areas
- Disruption of air flow are prevented
  with large spatial separation
  of air entry and exit points